Inspection and verification

How to Calculate Fuel Quantity in a Bunker Survey

2015-12-26 10:02:43 | Lượt xem: 3653 | Inspection and verification

A worked example of calculating bunker fuel quantity from tank measurements, temperature and density: interpolate volume, apply VCF/WCF and check units before reporting.

Đọc bài viết bằng tiếng Việt →

During a marine bunker survey, tank measurements and correction factors determine the calculated fuel quantity. The following example shows how to interpolate the volume and convert it to mass for one FO tank.

1. Data to collect

  • The sounding measurement and tank capacity tables. Where required, correct the sounding for the vessel's trim and list before using the tables.
  • The fuel temperature in the tank.
  • The fuel density at 15°C, with its units clearly stated.
  • The volume correction factor (VCF) and weight conversion factor (WCF) from the applicable tables. The original example uses ASTM Tables 54B and 56.

2. Example input data

ParameterValue
TankFO No. 1 Centre
Corrected sounding3.27 m
Fuel temperature34°C
Density at 15°C0.9903 t/m³ (equivalent to 0.9903 kg/L)
Tabulated volume at a sounding of 3.20 m157.20 m³
Tabulated volume at a sounding of 3.30 m163.60 m³

3. Interpolate the observed volume

V = 157.20 + [(3.27 − 3.20) / (3.30 − 3.20)] × (163.60 − 157.20)
V = 161.68 m³

Interpolation uses two adjacent entries in the tank capacity table. Make sure that the correct tank table and correction conditions are used.

4. Convert volume to mass

In the original article's illustrative data, at 34°C and a density of 0.9903 t/m³, the VCF is taken as 0.9870 and the WCF as 0.9892 t/m³. These factors apply only to this example and must not be assumed for every fuel consignment.

Mass (tonnes) = Observed volume (m³) × VCF × WCF (t/m³)
= 161.68 × 0.9870 × 0.9892
≈ 157.85 tonnes
Correction-factor table used in the fuel quantity example
Correction-factor table used in the fuel quantity example

The original article describes estimating WCF as density at 15°C minus 0.0011, when density is expressed in t/m³. For an official report, use the method and factors appropriate to the agreed mass calculation basis; a general shortcut formula must not replace checking the applicable tables.

5. Checks before preparing the report

  • Check that the units are consistent: m³, kL, metric tonnes and density.
  • For data expressed in barrels, use the corresponding tables and conversion factors; the original article refers to ASTM Tables 6B, 11 and 13.
  • Calculate each tank separately, record the data sources and round only at the final reporting stage.
  • Cross-check the attached calculation sheet; the correct temperature for this example is 34°C.
Tank sounding and fuel quantity calculation sheet
Tank sounding and fuel quantity calculation sheet

ITVC performs bunker surveys in Hai Phong, Ho Chi Minh City, Da Nang, Nghi Son, Vung Tau, Phu My and other requested locations.

ITVC GLOBAL · SERVICE ENQUIRIES

Discuss your marine bunker survey requirements with ITVC

Share your requirements and preferred timing. ITVC will review your enquiry and discuss a suitable service scope.

Send a service request →

Call for quotation: 0914 564 579
Ho Chi Minh City: 0859 553 986
Email: itvc.haiphong@itvc-global.com

Head office: 6th Floor, 22 Ly Tu Trong, Hong Bang Ward, Hai Phong, Vietnam.




Copyright © 2014 ICTV. All Rights Reserved.

tư vấn iso, tu van iso, kiểm toán năng lượng, kiem toan nang luong

0914 564 579