Common LS inverter faults: symptoms and checks

2015-10-31 08:15:09 | Lượt xem: 7630 | Energy and greenhouse gases

ITVC Global summarises several faults that may occur when using LS inverters. Check the manual for the specific drive model before diagnosis or maintenance.

The display codes below are retained from the original images. Check the exact drive model and manufacturer manual. Electrical inspection, disconnection and maintenance must be performed by qualified personnel after isolation and confirmation of safe conditions under the equipment instructions.

OCt — Overcurrent

Original image: inverter technical support 1
Original display code: OCt

(Overcurrent): a commonly encountered trip. The original article identifies the following possible conditions to investigate.

  • A seized motor shaft or damaged bearings.
  • An excessive load causing a sudden rise in current.
  • Damaged wiring or a lost phase between the drive and motor. The original article particularly mentions systems using slip rings or quick connectors; confirm the actual fault code against the model manual.

OLt — Overload

Original image: inverter technical support 2
Original display code: OLt

(Overload)

  • A motor or load that exceeds the drive's rating.
  • An excessively long motor cable is another condition the original article recommends checking against the manufacturer's permitted cable length and installation requirements.

FAN — Cooling-fan fault

Original image: inverter technical support 3
Original display code: FAN

(Cooling-fan fault)

  • A failed cooling fan or damaged fan-supply wiring. The original article notes that exposed wiring may be damaged by insects.

OHt — Overheating

Original image: inverter technical support 4
Original display code: OHt

(Overheating)

  • The heat-sink temperature exceeds its permitted limit. This differs from a fan-fault alarm: the fan may still operate, but a hot installation environment or inadequate ventilation can prevent effective cooling.

OUt — Overvoltage

Original image: inverter technical support 5
Original display code: OUt

(Overvoltage): the drive's DC-link voltage exceeds the permitted value. The original article also points to mechanical load conditions that should be assessed during diagnosis.

  • An excessively slack drive chain or belt.
  • Uneven or eccentric loads, such as rice-screening machinery or rotary tables. Braking arrangements, including a suitable braking resistor where required, must be selected according to the drive manufacturer's instructions and the actual regenerative load.

rErr — Keypad communication fault

Original image: inverter technical support 6
Original display code: rErr

(Communication fault)

  • A poor connection in the communication cable between the keypad and drive. Connections may have been affected during transport or installation and should be inspected by a qualified technician after safe isolation.

HWt — Hardware fault

Original image: inverter technical support 7
Original display code: HWt

(Hardware fault): refer the drive to the supplier or an authorised service centre. This is beyond routine operator troubleshooting.

These are examples of common faults; the correct diagnosis depends on the drive model, fault code and operating conditions.

LS Electric — iG5A manual

ITVC GLOBAL · SERVICE ENQUIRIES

Discuss inverter technical support with ITVC

Share your requirements and preferred timing. ITVC will review your enquiry and discuss a suitable service scope.

Send a service request →

Call for quotation: 0914 564 579
Ho Chi Minh City: 0859 553 986
Email: itvc.haiphong@itvc-global.com

Head office: 6th Floor, 22 Ly Tu Trong, Hong Bang Ward, Hai Phong, Vietnam.




Copyright © 2014 ICTV. All Rights Reserved.

tư vấn iso, tu van iso, kiểm toán năng lượng, kiem toan nang luong

0914 564 579