A reference to selected MICROMASTER 4 fault codes and diagnostic considerations for qualified personnel. Codes and parameters depend on model, rating and firmware; use the appropriate Siemens documentation and safe isolation procedures before intervention.
Drive inspection and repair require qualified personnel. Before opening equipment, isolate the supply, observe the model’s capacitor-discharge time and verify safe conditions. Correct the cause before acknowledgement; do not repeatedly reset or disable protection.
Variable-speed drive inspection and repair illustration
Siemens drives are used in many industrial applications. When a drive trips, it stops operation and displays a fault code on its BOP or AOP operator panel.
After identifying and correcting the cause and confirming that a restart is safe, the model’s documented acknowledgement methods may include:
Cycling the supply in accordance with the model’s instructions and required discharge time.
Using the acknowledgement function on the BOP or AOP.
Using the configured digital acknowledgement input; digital input 3 is a default arrangement on some models and may have been changed.
Selected MICROMASTER 4-series fault codes
1. F0001 — Overcurrent
Fault acknowledgement and diagnostic records
Use the documented power-cycle method only after correcting the cause and confirming a safe restart.
Use the panel’s acknowledgement function where appropriate.
Check the model-specific settings for fault acknowledgement, including P2103 and P2104 where applicable.
P0952 concerns the stored fault count/history. Clearing history is not a repair and must not replace diagnosis of an active fault.
A recurring fault does not by itself prove hardware failure. Check the supply, load, motor, cabling, parameters and drive before deciding on repair.
Possible causes
An output short circuit.
An earth fault.
Motor power outside the drive’s suitable range.
Unsuitable parameter settings.
Checks and corrective work for qualified personnel
Confirm that motor-cable length is within the permitted limit.
Check the motor and cable for short circuits and earth faults using an appropriate isolated test procedure.
Check the motor data and stator-resistance parameter P0350 where applicable.
Check for a jammed shaft or excessive mechanical load.
Review acceleration time and adjust only within the application’s safe operating requirements.
Review motor–drive sizing; changing motor size requires an application assessment.
2. F0002 — Overvoltage
Possible causes
DC-link voltage above the permitted threshold.
Excessive supply voltage or regenerative energy during deceleration or driven-load operation.
Checks and corrective work
Check supply voltage and the applicable P0210 setting.
Review the DC-link voltage controller configuration for the model.
Review ramp-down and OFF3 ramp-down settings, including P1121 and P1135 where applicable.
Investigate any accompanying insulation or earth-fault indication.
Check the braking arrangement, ratings and related settings, including the braking resistor where fitted.
3. F0003 — Undervoltage
Possible causes
A mains-supply failure or voltage dip.
A sudden load outside the specified limits.
A hardware problem requiring diagnosis.
Checks and corrective work
Check supply voltage, stability and quality.
If supply and installation checks do not explain the fault, arrange qualified hardware diagnosis.
Discuss drive repair with ITVC
Call ITVC to discuss your needs and a suitable service approach.
Excessive internal temperature. Read r0037 as applicable; P0292 defines the difference between warning and trip temperatures, not a freely adjustable trip limit.
Checks and corrective work
Check cooling-fan operation against the model’s control sequence.
Check that switching frequency is within the permitted range for the load and conditions.
Check ambient temperature against the equipment limits.
Review load and restore adequate cooling.
Additional diagnostics for applicable FX and GX frame sizes
r0949 = 1: rectifier overtemperature.
r0949 = 2: excessive ambient temperature.
r0949 = 3: EBOX overtemperature.
5. F0005 — Drive I²t overload
Possible causes
Drive overload.
A demanding duty cycle, including rapid repeated speed changes or reversals.
A motor rating incompatible with the drive.
The calculated overload limit has been reached.
Checks and corrective work
Review the duty cycle and acceleration and deceleration times.
Check motor and drive rating compatibility.
6. F0011 — Motor overtemperature
Possible cause
Motor overload.
Checks and corrective work
Review the duty cycle.
Check relevant thermal parameters, including P0626–P0628 where applicable.
Check that the motor warning-temperature setting P0604 is appropriate.
Check for excessive voltage boost or operation at a frequency too low for the required load and cooling.
Check motor cooling conditions.
7. F0012 — Drive temperature-sensor signal lost
Possible cause: a fault in the drive’s temperature-sensing circuit.
Qualified personnel should inspect the sensor circuit and connections using the model-specific service instructions.
8. F0015 — Motor temperature-sensor fault
Possible cause: an open circuit or short circuit in the motor temperature-sensing circuit.
Check the sensor type, configuration, wiring and connections.
9. F0020 — Input phase loss
Read the associated diagnostics and follow the model-specific acknowledgement procedure.
Possible cause: loss of one input phase.
Qualified personnel should inspect the incoming supply and three-phase connections after safe isolation.
10. F0021 — Earth fault
On applicable models, this diagnostic monitors an imbalance in the sum of the phase currents. The original reference describes a threshold above 5% of rated drive current for certain three-current-transformer configurations in frame sizes D–F; confirm applicability in the specific manual.
Discuss drive diagnosis with ITVC
Send your requirements so ITVC can advise on the service scope and provide a suitable quotation.